Liebert Trinergy™ Cube MECHANICAL INSTALLATION
Page 10 Installation Manual - 10H52243IM60 - rev. 7 - 06/2020
2.5.2. Storing the UPS and Batteries for Delayed Installation
If the UPS system will not be installed immediately, store it indoors in a clean, dry, and cool location (see
chap. 8. on page 129 and chap. 9. on page 131). If the system includes a battery cabinet, the batteries’
requirements dictate the storage conditions. Unpacked, install, and charge batteries as soon as possible
after delivery.
Notice
There is a potential risk to the operational integrity of an installed UPS system by the presence of foreign
material inside or in the vicinity of the UPS module. This risk is especially high if conductive materials find
their way inside the UPS module. The risk potentially involves damage to the installed UPS equipment and
subsequent degradation or loss of power to the connected critical site load. Vertiv applies the highest safety
standards in equipment design to ensure that no live parts are exposed to external contact, and also to
ensure that the equipment is protected against the introduction of foreign bodies during operation.
However, it is not possible for Vertiv. to ensure that foreign bodies will not be introduced during on-site
installation, or when the UPS doors and covers are open and the electrical terminals are exposed to allow
power line connections to be made by the electrical contractor/installer. To prevent major disruption to site
operations and risk to property and personnel, including the possibility of a fatality, each site’s facility
manager or construction manager must prevent foreign bodies from being introduced into the UPS module.
All UPS modules are thoroughly inspected by Vertiv engineers before being placed into service and testing
on-site. However, the person responsible for the site must ensure that the UPS module and the immediate
surroundings are kept clean and free from any possible conductive material such as metal foil, food
wrappers, cable shields, washers and other hardware, scrap metal and dust. If the UPS system is shut-down
after placement into service and testing are completed, the UPS room must be kept clean to avoid the
possibility (during restart) of the considerable volume of air-flow produced by UPS operation to dislodge
and/or drag any foreign bodies into the equipment, which would result in system failure and possible supply
interruption to the critical site load, and several hours of downtime resulting from the damage typically
associated with such events. If the UPS is left running/operational after placement into service and testing,
the room must be kept clean to prevent foreign bodies from entering the UPS module via its forced air-flow.
Notice
Ensure the top of the UPS is protected from any metal shaving or debris by using the temporary external
filter material that shipped with the UPS. It is the responsibility of the installer to ensure no conductive
material enters the unit. Installer will be billed at Vertiv’s prevailing labor wage for any cleaning or failure
as a result of debris entering the unit
Notice
Risk of failure to properly charge batteries. Can cause permanent damage to batteries and void the
warranty. Batteries will discharge during storage. Batteries must be recharged as recommended by the
battery manufacturer. Storage at a higher temperature will increase the rate of self-discharge, which
requires earlier recharge. Consult the battery manufacturer on how to determine when the batteries need
to be recharged.

Table of Contents

Other manuals for Vertiv Liebert Trinergy Cube

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert Trinergy Cube and is the answer not in the manual?

Vertiv Liebert Trinergy Cube Specifications

General IconGeneral
BrandVertiv
ModelLiebert Trinergy Cube
CategoryUPS
LanguageEnglish

Related product manuals