Technical data - SYSTEM Liebert Trinergy™ Cube
Installation Manual - 10H52243IM60 - rev. 7 - 06/2020 Page 131
9. TECHNICAL DATA - SYSTEM
General conditions of technical data table:
The data shown are approximate and refer to the 200kVA and 400kVA rating, 20°C ambient temperature
and nominal input and output conditions, unless otherwise specified. Not all data shown apply
simultaneously. Data apply to the standard version, unless otherwise specified.
For test conditions and measurement tolerances not specified in the table, see the Witness Test Report
procedure.
BOX model
Rating (A) 600 1200 2400 3000 4000 5000
System data
Heat
dissipation
at nominal
output
load
2)
VFI
Float mode
(kW)
(Btu/h)
15
(49820) 52440
30.8
(105000)
61.6
(210000)
(92.3) 92.2
(315090) 314630
(123.1)
122.9
(420120)
419500
(153.9)
153.7
(525145)
524380
Recharge mode
at max available
recharging
current
(kW)
(Btu/h)
16
(54060) 56680
(35.7) 33
(121800) 113360
(71.4) 66.4
(243500) 226710
(107.0) 99.7
(365230) 340100
(143.8)
132.9
(486980)
453430
(178.4)
166.1
(608720)
566790
VI
Float mode
(kW)
(Btu/h)
(5.4) 5.7
(18410) 19380
(10.2) 11.4
(34900) 38760
(20.4) 20.7
(69800) 77510
(30.7) 34.1
(104650) 116280
(40.9)
45.4
(139530)
155030
(51.1) 56.8
(174410)
193790
Recharge mode
at max available
recharging
current
(kW)
(Btu/h)
7
(22650) 23620
(15.1) 14
(51600) 47240
(30.2) 28
(103200) 94480
(45.4) 42
(154790) 141720
(60.5) 55
(206400)
189000
(75.6) 69
(258000)
236200
VFD
Float mode
(kW)
(Btu/h)
(3.8) 4
(13100) 13790
(7.3) 8.1
(24820) 27570
(14.5) 16.2
(49630) 55140
(21.8) 24.2
(74450) 82720
(29.1)
32.3
(99280)
110300
(36.4)
40.4
(124100)
137900
Recharge mode
at max available
recharging
current
(kW)
(Btu/h)
5
(17340) 18030
(12.2) 11
(41530) 36050
(24.3) 21
(83060) 72100
(36.5) 32
(124590) 108160
(48.7) 42
(166117)
144220
(60.9) 53
(207650)
180300
Noise (dbA)
1)
72-79
Primary input
Nominal voltage (V)
2)
400 (3ph + N + PE) or 400 (3ph + PE)
Input voltage range (V) 200-460
Nominal frequency (Hz) 50 (60 selectable)
Maximum input current I
(max)
(A)
630 1250 2500 3200 4250 5000
System output
3)
Nominal output current (A) 600 1200 2400 3000 4000 5000
Bypass input
Nominal output voltage (Vrms) 400 (3ph + N + PE) or 400 (3ph + PE)
Selectable output voltage (Vrms) 380, 400, 415, 440
Voltage range (%) 10 (5 to 15 selectable)
Nominal frequency (Hz) 50 (60 selectable)
Frequency range (%) ±2 (2, 3, 4,5 selectable)