cli->breakerstate 2.B
[2] --- (B) Close
2.6 buzzer
Type buzzer to facilitate enabling and disabling of the buzzer. This command is available for an admin, appliance or
poweruser.
NOTE: This command is supported for the rack PDU array level, but not for an individual rack PDU.
buzzer
help
enable
disable
Table 2.5 Syntax
Example
To enable the buzzer, enter the following command.
cli->buzzer enable
2.7 crestfactor
Type crestfactor to display the AC current crest factor of the receptacles in a rack PDU or Rack PDU Array™. This
command is available for an admin, appliance or poweruser.
crestfactor
help
<pdu>
<pdu.branch>
<pdu.branch.receptacle>
Table 2.6 Syntax
Examples
To view the crest factor for PDU2, enter the following command.
cli->crestfactor 2
[2.A] --- (1) 1.38 (2) 1.40 (3) 1.41 (4) 1.41 (5) 1.39 (6) 1.39
Vertiv | RPC2™ Communications Module Command Reference Guide | 8