help
address
<pdu>, <pdu.sensor>
alarm
<sensor type>(door, contact)
<pdu>, <pdu.sensor>, <pdu.sensor.cnct>
<event_type> (open, close)
<alarm_type>(none, open_alarm, close_alarm)
discover
<pdu>
order
<pdu>
<pdu-sensor> (from)
<pdu-sensor>(to)
threshold
<sensor type>(humidity, pressure, temperature)
<pdu>, <pdu.sensor>
<value>(high_critical, high_warn, low_critical, low_warn)
unit
<unit type>(celsius or fahrenheit)
<sensor_type>
<pdu>
<pdu.sensor>
<pdu.sensor.cnct>
Examples
To view the humidity on PDU3, enter the following command.
cli->sensor humidity 3
[3] --- (2) 60.0 % (4) 42.8 %
To enable the Contact Open alarm for contact 2 of sensor 1 on PDU3, enter the following command.
cli->sensor alarm contact 3.1.2 open alarm
2.30 snmp
Type snmp to permit an admin to view and configure SNMPsettings for a rack PDU or Rack PDU Array.
Vertiv | RPC2™ Communications Module Command Reference Guide | 32