[2.B] --- (1) 1.39 (2) 1.40 (3) 0.00 (4) 0.00 (5) 1.39 (6) 1.40
[2.C] --- (1) 1.41 (2) 1.40 (3) 1.39 (4) 0.00 (5) 0.00 (6) 0.00
To view the crest factor of branch Aof PDU2, enter the following command.
cli->crestfactor 2.A
[2.A] --- (1) 1.38 (2) 1.40 (3) 1.41 (4) 1.41 (5) 1.39 (6) 1.39
To view the crest factor of the sixth receptacle of branch Cof PDU2, enter the following command.
cli->crestfactor 2.C.6
[2.C] --- (6) 1.41
2.8 current
Type current to display the following at the input phase, branch and receptacle levels in a rack PDU or Rack PDUArray™.
• The metered reading of the AC current (RMS).
• The configurable threshold values for current.
• The amount of current increase allowed before the overcurrent alarm occurs.
• The percentage of receptacle current utilization relative to the receptacle’s current rating.
This command is available for an admin, appliance or poweruser.
Neutral current measurement and threshold settings are possible only at the PDU level for models having a neutral
connection. Except for neutral current, threshold values are colon-separated values in the following order: {high_critical}:
{high_warn}:{low_critical}.
NOTE: There is no {low_warn} threshold in a Vertiv MPH or MPX™ rack PDU.
If any threshold is not provided, the same has to be denoted with a hyphen “-” for example, {high_critical}:-:{low_critical}. For
neutral current, threshold values are colon-separated values in the following order: {high_critical}:{high_warn}. The {low_
critical} threshold does not exist for neutral current. Threshold current values are also expressed as a percentage of the
rated current value.
NOTE: Threshold values (high critical, high warning and low critical)have ranges of 0-100.
current
help
<pdu>
<phase>
Table 2.7 Syntax
Vertiv | RPC2™ Communications Module Command Reference Guide | 9