enable
disable
Example
To disable the software overcurrent protection for branch Cof PDU2, enter the following command.
cli->swocp 2.C disable
2.33 swotp
Type swotp to enable or disable the software overtemperature protection (SWOTP)at the PDU or receptacle level in a
rack PDU or Rack PDU Array™. This command is available for an admin, appliance or poweruser.
swotp
help
<pdu>, <pdu.branch>
enable
disable
Table 2.29 Syntax
Example
To disable the software overtemperature protection for branch Cof PDU2, enter the following command.
cli->swotp 2.C disable
2.34 sysinfo
Type sysinfo to display system information for a PDU, branch or receptacle in a rack PDU / Rack PDU Array™. This
command is available for an admin, appliance or poweruser.
sysinfo
help
arraysize
capabilities
<pdu>, <pdu.branch>, <pdu.branch.receptacle>
count
branch
<pdu>
receptacle
<pdu>, <pdu.branch>
sensor
<pdu>
Table 2.30 Syntax
Vertiv | RPC2™ Communications Module Command Reference Guide | 37