SNMP V1/V2 ............................enabled
To configure 162 as the SNMPTraps UPDport, enter the following command.
cli->snmp traps udpport 162
To configure SNMP traps to SNMPv1, enter the following command.
cli->snmp traps SNMPV1
To disable SNMPv3 ID2 traps notification, enter the following command.
cli->snmp v3 traps notify 2 disable
To configure an address as the SNMPv3 ID1 traps destination, enter the following command.
cli->snmp v3 traps destination 1 <ip address>
2.31 status
Type status to display the status of the overcurrent, undercurrent, undervoltage, channel at the PDU, branch or receptacle
level in a a rack PDU / Rack PDU Array.
status
help
channel
<pdu>, <pdu.branch>, <pdu.branch.receptacle>
overcurrent
<pdu>
<phase>
<pdu.branch>
<pdu.branch.receptacle>
undercurrent
<pdu>
<pdu.branch>
<phase>
pdu.branch.receptacle>
undervoltage
<pdu>
<phase>
Table 2.27 Syntax
Vertiv | RPC2™ Communications Module Command Reference Guide | 35