Example
To view power information for the phase L1 of PDU1, enter the following command.
cli->power 1 L12
1] --- (L2) 0.3 W : 0.4 VA
2.25 powerfactor
Type powerfactor to display the alternating current power factor (watt/VA)for a PDU, branch or receptacle in a rack PDU
or Rack PDU Array™. This command is available for an admin, appliance or poweruser.
powerfactor
help
<pdu>
<phase>
<phasepair>
<pdu.branch>
<pdu.branch.receptacle>
Table 2.20 Syntax
Example
To view powerfactor information for branch Aof PDU2, enter the following command.
cli->powerfactor 2.A
[2] --- (A) 0.85
CAUTION: powerupstate
Type powerupstate to permit a user to configure the receptacle power states after a power cycle. Setting it to on
configures all receptacles to be turned on after the power cycle. Setting it to off configures all receptacles to remain off
after the power cycle. Setting it to restore configures all receptacles to return to the state they were at before the power
cycle.
NOTE: This feature is only supported for MPH2 PDUs, not MPH or MPX PDUs.
powerupstate
help
<pdu>
Table 2.21 Syntax
Vertiv | RPC2™ Communications Module Command Reference Guide | 27