cli->datalog export_ftp filedir <file directory>
cli->datalog export_ftp filename <file name>
2.10 delay
Type delay to display values and facilitate configuration for poweron, post on and post off time delay at the receptacle
level. This command is available for an admin, appliance or poweruser.
delay
help
poweron
<pdu>
<pdu.branch>
<pdu.branch.receptacle>
post_on
<pdu>
<pdu.branch>
<pdu.branch.receptacle>
post_off
<pdu>
<pdu.branch>
<pdu.branch.receptacle>
Table 2.9 Syntax
Examples
To view the post-off delay for the sixth receptacle on branch Cof PDU2, enter the following command.
cli-> delay post_off 2.C.6
[2.C] --- (6) 1 s
To configure the poweron at 5 seconds and the post on and post off at 1 second each for all of PDU2, enter the following
command.
cli->delay 2 5:1:1
2.11 devicechange
Type devicechange to acknowledge and display the module change status information for an admin.
Vertiv | RPC2™ Communications Module Command Reference Guide | 14