<pdu.branch>
<pdu.branch.receptacle>
on, off, restore
Examples
The following examples shows you how to view and change the powerupstate information for branch A of PDU 1.
[1.A]---(1) On (2) restore (3) restore (4) restore
[1.B]---(1) restore (2) restore (3) restore
cli-> powerupstate 1.B.3 off
cli-> powerupstate
[1.A]---(1) On (2) restore (3) restore (4) restore
[1.B]---(1) restore (2) restore (3) Off (4) restore
2.26 reboot
Type reboot to enable an admin or appliance user to reboot the module or a specific PDU.
reboot
help
<pdu>
Table 2.22 Syntax
Example
To reboot PDU2 in an array, enter the following command.
cli->reboot 2
2.27 receptaclegroup
Type receptaclegroup to permit an admin to configure the receptacle group parameters for a rack PDU or Rack PDU
Array™.
Vertiv | RPC2™ Communications Module Command Reference Guide | 28