n Short description:
The short description of the Siemens CPU 313-6CF03 is CPU
313C-2DP.
n Order No. / Firmware:
Order number and firmware are identical to the details in the
"hardware catalog" window.
n Name:
The Name field provides the short description of the CPU. If you
change the name the new name appears in the Siemens
SIMATIC Manager.
n Interface:
Here is the address of the MPI interface.
n Properties:
By means of this button you can change the properties of the MPI
interface.
n Comment:
In this field information about the module may be entered.
n Startup when expected/actual configuration differs:
If the checkbox for ‘Startup when expected/actual configuration
differ’ is deselected and at least one module is not located at its
configured slot or if another type of module is inserted there
instead, then the CPU does not switch to RUN mode and remains
in STOP mode. If the checkbox for ‘Startup when expected/actual
configuration differ’ is selected, then the CPU starts even if there
are modules not located in their configured slots of if another type
of module is inserted there instead, such as during an initial
system start-up.
n Monitoring time for ready message by modules [100ms]:
This operation specifies the maximum time for the ready message
of every configured module after PowerON. Here connected
PROFIBUS DP slaves are also considered until they are parame-
terized. If the modules do not send a ready message to the CPU
by the time the monitoring time has expired, the actual configura-
tion becomes unequal to the preset configuration.
n Transfer of parameters to modules [100ms]:
The maximum time for the transfer of parameters to parameteriz-
able modules. If not every module has been assigned parameters
by the time this monitoring time has expired; the actual configura-
tion becomes unequal to the preset configuration.
n Update OB1 process image cyclically:
This parameter is not relevant.
n Scan cycle monitoring time:
Here the scan cycle monitoring time in milliseconds may be set. If
the scan cycle time exceeds the scan cycle monitoring time, the
CPU enters the STOP mode.
Possible reasons for exceeding the time are:
–
Communication processes
– a series of interrupt events
– an error in the CPU program
n Minimum scan cycle time:
This parameter is not relevant.
n Scan cycle load from Communication:
This parameter is not relevant.
General
Startup
Cycle/Clock memory
VIPA System 300SDeployment CPU 313-6CF13
CPU parametrization > CPU parameters
HB140 | CPU-SC | 313-6CF13 | GB | 15-50 54