6 Deployment I/O periphery
6.1 Overview
At the 313-6CF13 the connectors for digital in-/output and technolog-
ical functions are integrated to a 2tier casing.
The project engineering takes place in the Siemens SIMATIC man-
ager as CPU 313C-2DP from Siemens (6ES7 313-6CF03-0AB0
V2.6). Here the CPU 313-6CF13 is parameterized by the "Properties"
dialog of the CPU 313C-2DP. For parameterization of the digital I/O
periphery and the technological functions the corresponding sub-
module of the CPU 313C-2DP may be used.
The integrated I/Os of the 313-6CF13 may be used for technological
functions or as standard I/Os. Technological functions and standard I/
Os may be used simultaneously with appropriate hardware. Read
access to inputs used by technological functions is possible. Write
access to used outputs is not possible.
Up to 3 channels may be parameterized as technological function.
The parameterization of the appropriate channel is made in the hard-
ware configurator by the count submodule of the CPU 313C-2DP.
There are the following technological functions:
n Continuous count
n Single count
n Periodic count
n Frequency measurement
n Pulse width modulation (PWM)
The controlling of the corresponding counter mode happens by
means of the SFB COUNT (SFB 47) of the user program.
Hardware
Project engineering
I/O periphery
Technological functions
VIPA System 300SDeployment I/O periphery
Overview
HB140 | CPU-SC | 313-6CF13 | GB | 15-50 96