1.
Perform a hardware configuration for the CPU.
Ä
Chapter 5.5
‘Hardware configuration - CPU’ on page 50
2. Configure always as last module a Siemens DP master CP
342-5 (342-5DA02 V5.0). Connect and parameterize it at opera-
tion mode "DP-Master".
3. Connect the slave system "VIPA_SPEEDbus". After installing
the SPEEDBUS.GSD this may be found in the hardware catalog
at Profibus-DP / Additional field devices / I/O / VIPA /
VIPA_SPEEDBUS.
4. For the slave system set the PROFIBUS address 100.
5. Configure at slot 0 the VIPA CPU 313-6CF13 of the hardware
catalog from VIPA_SPEEDbus.
6. By double clicking the placed CPU 313-6CF13 the properties
dialog of the CPU may be opened.
The hardware configuration, which is shown here, is only
required, if you want to customize the VIPA specific
parameters.
5.9.2 VIPA specific parameters
The following parameters may be accessed by means of the proper-
ties dialog of the VIPA CPU.
5.9.2.1
Function RS485 X3
Using this parameter the RS485 interface may be switched to PtP
communication (point to point) respectively the synchronization
between DP master system and CPU may be set:
Deactivated Deactivates the RS485 interface.
PtP With this operating mode the
PROFIBUS DP master is deacti-
vated and the RS485 interface
acts as an interface for serial
point-to-point communication.
Here data may be exchanged
between two stations by means
of protocols.
PROFIBUS DP async PROFIBUS DP master operation
asynchronous to CPU cycle The
RS485 interface is preset at
default to PROFIBUS DP async.
Here CPU cycle and cycles of
every VIPA PROFIBUS DP
master run independently.
PROFIBUS DP syncIn The CPU is waiting for DP
master input data.
VIPA System 300SDeployment CPU 313-6CF13
Setting VIPA specific CPU parameters > VIPA specific parameters
HB140 | CPU-SC | 313-6CF13 | GB | 15-50 58