WAGO I/O SYSTEM 750 XTR Use in Hazardous Environments 367
750-8202/040-000 PFC200 2ETH RS XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
15.2.2 Special Notes Regarding ANSI/ISA Ex
For ANSI/ISA Ex acc. to UL File E198726, the following additional requirements
apply:
Use in Class I, Division 2, Group A, B, C, D or non-hazardous areas only
ETHERNET connections are used exclusively for connecting to computer
networks (LANs) and may not be connected to telephone networks or
telecommunication cables
WARNINGThe radio receiver module 750-642 may only be used to
connect to external antenna 758-910!
WARNINGProduct components with fuses must not be fitted into circuits
subject to overloads!
These include, e.g., motor circuits.
WARNINGWhen installing I/O module 750-538, “Control Drawing No.
750538” in the manual must be strictly observed!
Additional Information
Proof of certification is available on request.
Also take note of the information given on the operating and assembly
instructions.
The manual, containing these special conditions for safe use, must be readily
available to the user.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO PFC200 2ETH RS XTR and is the answer not in the manual?

WAGO PFC200 2ETH RS XTR Specifications

General IconGeneral
ProcessorARM Cortex-A8
Clock Speed600 MHz
RAM256 MB
Ethernet Ports2
Protection ClassIP20
Power Supply24 V DC
Serial Ports1 (RS-232/RS-485)
Operating Temperature-40°C to +70°C
Programming LanguagesIEC 61131-3
CertificationsUL