6 2576780000/00/02-2018
Product description
Scope of delivery Energy Meter 610 or 610-PB
Quantity Designation
1 Energy Meter 610 or 610-PB
2 Mounting brackets
1 Quick guide
1 Screw terminal, pluggable, 2-pin (auxiliary energy)
1 Screw terminal, pluggable, 4-pin (voltage measure-
ment)
1 Screw terminal, pluggable, 6-pin (current measure-
ment)
1 Screw terminal, pluggable, 2-pole (current measure-
ment I4)
1 Screw terminal, pluggable, 2-pin (RS 485)
1 Screw terminal, pluggable, 10-pole (digital inputs/
outputs)
1 Screw terminal, pluggable, 3-pin (digital/pulse
output)
Product description
Proper use
The Energy Meter 610/610-PB is intended for the measurement
and calculation of electrical parameters such as voltage, current,
power, energy, harmonics etc. in building installations, on distribu-
tion units, circuit breakers and busbar trunking systems.
The Energy Meter 610/610-PB is suitable for integration into xed
and weatherproof switch panels. Conductive switch panels must
be earthed. Can be installed in any attitude.
Measured voltage and measured current must derive from the
same network.
The measurement results can be displayed and can be read out
and further processed via the interfaces.
The voltage measurement inputs are designed for measurements
in low voltage networks, in which rated voltages of up to 300 V
relative to earth and surges in overvoltage category III can occur.
The current measurement inputs of the Energy Meter 610/610-PB
are connected via external ../1A or ../5A current transformers.
The measurement in medium and high voltage networks is im-
plemented in principle via current and voltage transformers. The
Energy Meter 610/610-PB can be employed both domestically and
in industry.
Device characteristics
• Supply voltage
Option 230 V: 90 to 277 V (50/60 Hz) or
DC 90 to 250 V; 300 V CATIII
Option 24 V: 24 to 90 V AC/DC; 150V CATIII
• Frequency range: 45 to 65 Hz
Device functions
Energy Meter
610-PB 610
3 voltage measurements, 300 V
4 current measurements (via current trans-
former)
RS 485 interface (Modbus RTU)
Probus
–
USB
2 + 4 digital outputs
4 digital inputs
Clock, memory