Technical Data
Parameters of functions
Function Symbol Accuracy class Metering range Display range
Total real power P 0.5
5)
(IEC 61557-12) 0 to 5.4 kW 0 W to 999 GW *
Total reactive power
QA, Qv
1 (IEC 61557-12) 0 to 5.4 kvar 0 varh to 999 Gvar *
Total apparent power
SA, Sv
0.5
5)
(IEC 61557-12) 0 to 5.4 kVA 0 VA to 999 GVA *
Total active energy Ea 0.5S
5) 6)
(IEC 61557-12) 0 to 5.4 kWh 0 Wh to 999 GWh *
Total reactive energy
ErA, ErV
1 (IEC 61557-12) 0 to 5.4 kvarh 0 varh to 999 Gvarh *
Total apparent energy
EapA, EapV
0.5
5)
(IEC 61557-12) 0 to 5.4 kVAh 0 VAh to 999 GVAh *
Frequency f 0.05 (IEC 61557-12) 45 to 65 Hz 45.00 Hz to 65.00 Hz
Phase current I 0.2 (IEC 61557-12) 0 to 6 Arms 0 A to 999 kA
Measured neutral conductor current IN 1 (IEC 61557-12) 0 to 6 Arms 0 A to 999 kA
Calculated neutral conductor current INc 1 (IEC 61557-12) 0.03 to 25 A 0.03 A to 999 kA
Voltage U L-N 0.2 (IEC 61557-12) 10 to 300 Vrms 0 V to 999 kV
Voltage U L-L 0.2 (IEC 61557-12) 18 to 520 Vrms 0 V to 999 kV
Displacement factor PFA, PFV 0.5 (IEC 61557-12) 0.00 to 1.00 0.00 to 1.00
Short-term icker, long-term icker Pst, Plt - - -
Voltage dips (L-N) Udip - - -
Voltage surges (L-N) Uswl - - -
Transient overvoltages Utr - - -
Voltage interruptions Uint - - -
Voltage unbalance (L-N)
1)
Unba - - -
Voltage unbalance (L-N)
2)
Unb - - -
Voltage harmonics Uh Class 1 (IEC 61000-4-7) up to 2.5 kHz 0 V to 999 kV
THD of the voltage
3)
THDu 1.0 (IEC 61557-12) up to 2.5 kHz 0 % to 999 %
THD of the voltage
4)
THD-Ru - - -
Current harmonics Ih Class 1 (IEC 61000-4-7) up to 2.5 kHz 0 A to 999 kA
THD of the current
3)
THDi 1.0 (IEC 61557-12) up to 2.5 kHz 0 % to 999 %
THD of the current
4)
THD-Ri - - -
Mains signal voltage MSV - - -
1) Referred to amplitude.
2) Referred to phase and amplitude.
3) Referred to mains frequency.
4) Referred to root mean square value.
5) Accuracy class 0.5 with ../5A transformer.
Accuracy class 1 with ../1A transformer.
6) Accuracy class 0.5S according IEC 62053-22.
* The display returns to 0 W when the maximum total energy values are reached.