452576780000/00/02-2018
Service and maintenance
Comparators and monitoring threshold values
Six comparator groups (1 to 6) and three comparators per group
(A to C) can be selected in order to monitor/control the thresholds.
The results of the comparators A to J can be linked with AND or
OR operators.
The result of the AND and OR operator can be allocated to the
respective digital output.
The function “display blinking” can be additionally assigned to
every comparator group. The effect is the change of the display
backlight between maximum and minimum brightness when the
comparator output is active.
Fig.: Software ecoExplorer go, conguration menu
Service and maintenance
The device is subjected to several different safety tests before
leaving the factory and is labelled with a seal. If a device is opened
then the safety checks must be repeated. Warranty claims will only
be accepted if the device is unopened.
Repair and calibration
Repair work and calibration can be carried out by the manufacturer
only.
Front lm
The front lm can be cleaned with a soft cloth and standard house-
hold cleaning agent. Do not use acids and products containing
acid for cleaning.
Disposal
The Energy Meter 610/610-PB can be reused or recycled as elec-
tronic scrap in accordance with the legal provisions. The perma-
nently installed lithium battery must be disposed of separately.
Service
Should questions arise, which are not described in this manual,
please contact the manufacturer directly.
We will need the following information from you to answer any
questions:
- Device name (see rating plate),
- Serial number (see rating plate),
- Software release (see measured value display),
- Measuring-circuit voltage and power supply voltage,
- Precise description of the error.
Device calibration
The devices are calibrated by the manufacturer at the factory – it is
not necessary to recalibrate the device providing that the environ-
mental conditions are complied with.
Calibration intervals
It is recommended to have a new calibration carried out by the
manufacturer or an accredited laboratory every 5 years approxi-
mately.