Room temperature controller functions
32 | WOLF GmbH 3066510_202108
Index Meaning
Setting
range
Factory
setting
P 20
Minimum ow temperature
Room temperature control
10°C – 60°C 20
P 21
Maximum ow temperature
Room temperature control
25°C – 90°C 55°C
P 22 Economy temperature 10°C – 30°C 15°C
P 23
P component room
temperature control ***
1K/K – 50K/K 10K/K
P 24
I component room
temperature control ***
0.1K/(K/h) –
20K/(K/h)
6.0K/(K/h)
P 25
Outside temperature frost
protection limit
-20 to +10°C +2°C
P 30/
HG01*
Burner switching differential 5K to 25K 8K
P 31/
HG02*
Lower burner output, heating 1% to 100% 1%
P 32/
HG03*
Upper burner output DHW 1% to 100% 100%
P 33/
HG04*
Upper burner output, heating 1% to 100% 100%
P 34/
HG06*
Pump operating mode 0 to 2 0
P 35/
HG07*
Boiler circuit pump run-on
time
0 min to 30 min 1 min
P 36/
HG08*
Maximum boiler temperature,
heating
40°C to 90°C 80°C
P 37/
HG09*
Burner cycle block 1 min to 20 min 7 min
P 38/
HG13*
Programmable input E1 0 to 11 1
P 39/
HG14*
Programmable output A1 0 to 15 6
P 40/
HG16*
Minimum heating circuit
pump rate
20% to 100% 20%