Room temperature controller functions
3066510_202108 WOLF GmbH | 35
8.7 Holiday mode
► Press the key in the standard heating/DHW or ventilation
display.
– Navigation as per remote control!
Symbol Function
Holiday mode: Economy/reduced operation mode for
heating, standby for DHW and moisture protection for
ventilation for a predened period (15 min to 99 days)
8.8 Special functions
8.8.1 Room temperature-dependent set ow temperature
ϑFlow_set =
(ϑFlow_max + ϑFlow_min)
+ ϑP component + ϑI component
2
ϑFlow_set = Set ow temperature
ϑFlow_max = Maximum ow temperature (P21 Maximum Flow
Temperature)
ϑFlow_min = Minimum ow temperature (P20 Low End
Temperature)
ϑP component = A xed value is added to the set ow temperature if
the set room temperature deviates from the actual room temperature.
The factor can be set as parameter P23 “P component room
temperature control”.
Example:
Set temperature = 21.0°C;
actual temperature = 20.5°C -->
deviation = 0.5 K
If the factory setting of 10 K/K is applied, 0.5K*10K/K=5K is added to
the calculated set ow temperature.
ϑI component = A time-dependent value is added to the set ow
temperature if the set room temperature deviates from the actual
room temperature. The factor can be set as parameter P24 “I
component room temperature control”.
Example:
Set temperature = 21.0°C;
actual temperature = 20.0°C -->
deviation = 1 K
At the factory setting of 6K/(K/h), 1°C is added to the set ow value
every 10 minutes