Room temperature controller functions
3066510_202108 WOLF GmbH | 35
8.7 Holiday mode
Press the key in the standard heating/DHW or ventilation
display.
Navigation as per remote control!
Symbol Function
Holiday mode: Economy/reduced operation mode for
heating, standby for DHW and moisture protection for
ventilation for a predened period (15 min to 99 days)
8.8 Special functions
8.8.1 Room temperature-dependent set ow temperature
ϑFlow_set =
(ϑFlow_max + ϑFlow_min)
+ ϑP component + ϑI component
2
ϑFlow_set = Set ow temperature
ϑFlow_max = Maximum ow temperature (P21 Maximum Flow
Temperature)
ϑFlow_min = Minimum ow temperature (P20 Low End
Temperature)
ϑP component = A xed value is added to the set ow temperature if
the set room temperature deviates from the actual room temperature.
The factor can be set as parameter P23 “P component room
temperature control”.
Example:
Set temperature = 21.0°C;
actual temperature = 20.5°C -->
deviation = 0.5 K
If the factory setting of 10 K/K is applied, 0.5K*10K/K=5K is added to
the calculated set ow temperature.
ϑI component = A time-dependent value is added to the set ow
temperature if the set room temperature deviates from the actual
room temperature. The factor can be set as parameter P24 “I
component room temperature control”.
Example:
Set temperature = 21.0°C;
actual temperature = 20.0°C -->
deviation = 1 K
At the factory setting of 6K/(K/h), 1°C is added to the set ow value
every 10 minutes