Parameter List
1
1.5 b: Application
YASKAWA TOEPYAIGA5002A GA500 Programming 19
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b4-07
(0B34)
Expert
Terminal P2 ON-Delay
Time
Sets the delay time until the contact is turned ON after the function set with H2-03 turns
ON.
0 ms
(0 - 65000 ms)
181
b4-08
(0B35)
Expert
Terminal P2 OFF-Delay
Time
Sets the delay time to deactivate the contact after the function set in H2-03 deactivates.
0 ms
(0 - 65000 ms)
181
b5: PID control
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b5-01
(01A5)
PID Mode Setting
Sets the type of PID control.
0 : Disabled
1 : Standard
2 : Standard (D on feedback)
3 : Fref + PID Trim
4 : Fref + PID Trim (D on feedback)
5 : Same as 7series & prior, b5-01=1
6 : Same as 7series & prior, b5-01=2
7 : Same as 7series & prior, b5-01=3
8 : Same as 7series & prior, b5-01=4
Note:
Use settings 5 to 8 when the drive is a replacement for a previous generation drive.
0
(0 - 8)
187
b5-02
(01A6)
RUN
Proportional Gain (P)
Sets the proportional gain (P) that is applied to PID input.
1.00
(0.00 - 25.00)
188
b5-03
(01A7)
RUN
Integral Time (I)
Sets the integral time (I) that is applied to PID input.
1.0 s
(0.0 - 360.0 s)
188
b5-04
(01A8)
RUN
Integral Limit
Sets the upper limit for integral control (I) as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
100.0%
(0.0 - 100.0%)
188
b5-05
(01A9)
RUN
Derivative Time (D)
Sets the derivative time (D) for PID control. This parameter adjusts system responsiveness.
0.00 s
(0.00 - 10.00 s)
189
b5-06
(01AA)
RUN
PID Output Limit
Sets the maximum possible output from the PID controller as a percentage of the
Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
100.0%
(0.0 - 100.0%)
189
b5-07
(01AB)
RUN
PID Offset Adjustment
Sets the offset for the PID control output as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
0.0%
(-100.0 - +100.0%)
189
b5-08
(01AC)
RUN
Expert
PID Primary Delay Time
Constant
Sets the primary delay time constant for the PID control output. Usually it is not necessary
to change this setting.
0.00 s
(0.00 - 10.00 s)
189
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV