Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 Programming 311
Figure 2.71 Functional Block Diagram of Logical Operation Output for MFDO 1
Table 2.57 MFDO Logical Operation Table
Logical Operation Selection
Logical Operation Expression Logical Operation Notation
H2-61, H2-64, H2-67
0 A=B=1
1 A=1 or B=1
2 A=0 or B=0
3 A=B=0
4 A=B A=B
5 A != B
6
AND(A, )
7
OR(A, )
8 - On
Note:
• If you use the function to output logical calculation results, you cannot set H2-01 to H2-03 = 1xx [Inverse Output of xx]. If you do, the drive
will detect oPE33 [Digital Output Selection Error].
• When you do not use H2-60, H2-63, and H2-66, set them to F. The through mode function is not supported.
◆ H2 MFDO Parameters
■ H2-01: Term MA/MB-MC Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-01
(040B)
Term MA/MB-MC Function
Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
E
(0 - 1FF)
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through mode.
■ H2-02: Term P1-C1 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-02
(040C)
Term P1-C1 Function
Selection
Sets the function for MFDO terminal P1-C1.
0
(0 - 1FF)
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through mode.