1.8 E: Motor Parameters
34 YASKAWA TOEPYAIGA5002A GA500 Programming
1.8 E: Motor Parameters
E1: V/f Pattern for Motor 1
No.
(Hex.)
Name Description
Default
(Range)
Ref.
E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage.
NOTICE: Set parameter E1-01 to align with the drive input
voltage (not motor voltage). If this parameter is incorrect, the
protective functions of the drive will not operate correctly and it
can cause damage to the drive.
200 V Class: 240 V, 400
V: 480 V
(200 V Class: 155 to 255
V, 400 V Class: 310 to
510 V)
243
E1-03
(0302)
V/f Pattern Selection
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you
can make a custom pattern.
0 : Const Trq, 50Hz base, 50Hz max
1 : Const Trq, 60Hz base, 60Hz max
2 : Const Trq, 50Hz base, 60Hz max
3 : Const Trq, 60 Hz base, 72 Hz max
4 : VT, 50Hz, 65% Vmid reduction
5 : VT, 50Hz, 50% Vmid reduction
6 : VT, 60 Hz, 65% Vmid reduction
7 : VT, 60 Hz, 50% Vmid reduction
8 : High Trq, 50Hz, 25% Vmin Boost
9 : High Trq, 50Hz, 65% Vmin Boost
A : High Trq, 60 Hz, 25% Vmin Boost
B : High Trq, 60 Hz, 65% Vmin Boost
C : Const Trq, 60 Hz base, 90 Hz max
D : Const Trq, 60 Hz base, 120 Hz max
E : Const Trq, 60 Hz base, 180 Hz max
F : V/f Pattern Selection
Note:
When A1-02 = 2 [Control Method Selection = OLV], settings 0 to E are not
available.
Set the correct V/f pattern for the application and operation area. An incorrect V/f
pattern can decrease motor torque and increase current from overexcitation.
F
(Determined by A1-02)
243
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02
and E5-01)
248
E1-05
(0304)
Maximum Output Voltage
Sets the maximum output voltage for the V/f pattern.
200 V Class: 230.0 V, 400
V: 460.0 V
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
249
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(0.0 - E1-04)
249
E1-07
(0306)
Mid Point A Frequency
Sets a middle output frequency for the V/f pattern.
Determined by A1-02
(0.0 - E1-04)
249
E1-08
(0307)
Mid Point A Voltage
Sets a middle output voltage for the V/f pattern.
Determined by A1-02
C6-01 and o2-04
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
249
E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02,
E1-04, and E5-01)
249
E1-10
(0309)
Minimum Output Voltage
Sets the minimum output voltage for the V/f pattern.
Determined by A1-02
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to
510.0 V)
249
E1-11
(030A)
Expert
Mid Point B Frequency
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - E1-04)
249
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents