1.10 H: Terminal Functions
60 YASKAWA TOEPYAIGA5002A GA500 Programming
Setting Value Function Description Ref.
63 Modbus Reg 2 Status
Satisfied
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register
address set with H2-09 [Modbus Register 2 Address Select] activates.
330
66 Comparator1
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the values
of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24 [Comparator
1 On-Delay Time].
330
67 Comparator2
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of the
values of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-30
[Comparator 2 On-Delay Time].
331
69 External Power 24V
Supply
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
331
6A Data Logger Error
The terminal activates when the drive detects LoG [Com Error / Abnormal SD card].
331
90 - 92 DWEZ Digital Output 1
to 3
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
331
100 - 192 Inverse output of 0 to 92
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function
to inversely output.
331
◆ H3: Analog Inputs
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
4 : -10 to +10V (Bipolar Reference)
0
(0, 4)
334
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1.
0
(0 - 32)
334
H3-03
(0411)
RUN
Terminal A1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
334
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
334
H3-09
(0417)
Terminal A2 Signal Level
Select
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
4 : -10 to +10V (Bipolar Reference)
2
(0, 2 - 4)
335
H3-10
(0418)
Terminal A2 Function
Selection
Sets the function for MFAI terminal A2.
0
(0 - 32)
335
H3-11
(0419)
RUN
Terminal A2 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A2.
100.0%
(-999.9 - +999.9%)
335
H3-12
(041A)
RUN
Terminal A2 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A2.
0.0%
(-999.9 - +999.9%)
335
H3-13
(041B)
Analog Input FilterTime
Constant
Sets the time constant for primary delay filters on MFAI terminals.
0.03 s
(0.00 - 2.00 s)
336