EasyManua.ls Logo

YASKAWA GA500 series - Page 256

YASKAWA GA500 series
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.6 E: Motor Parameters
256 YASKAWA TOEPYAIGA5002A GA500 Programming
E4-02 = f - (n × p) / 120
f: Motor rated frequency (Hz)
n: Rated motor speed (min
-1
(r/min))
p: Number of motor poles
E4-03: Motor 2 Rated No-Load Current
No.
(Hex.)
Name Description
Default
(Range)
E4-03
(0323)
Motor 2 Rated No-Load
Current
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the no-load
voltage.
Determined by o2-04, C6-01
(0 to E4-01)
Note:
When the drive model changes, the display units for this parameter also change.
0.01 A: B001 - B018, 2001 - 2042, 4001 - 4023
0.1 A: 2056 - 2082, 4031 - 4060
You can also manually enter the motor no-load current shown on the motor test report to E4-03. Contact the motor
manufacturer for the motor test report.
Note:
The default setting of the no-load current is for a 4-pole motor recommended by Yaskawa.
E4-04: Motor 2 Motor Poles
No.
(Hex.)
Name Description
Default
(Range)
E4-04
(0324)
Motor 2 Motor Poles
Sets the number of poles for motor 2.
4
(2 - 120)
Auto-Tuning automatically sets E4-04 to the value input for [Number of Motor Poles].
E4-05: Motor 2 Line-to-Line Resistance
No.
(Hex.)
Name Description
Default
(Range)
E4-05
(0325)
Motor 2 Line-to-Line
Resistance
Sets the line-to-line resistance for the motor 2 stator windings.
Determined by o2-04, C6-01
(0.000 - 65.000 Ω)
Note:
This value is the line-to-line resistance for motor 2. Do not set this parameter with the per-phase resistance.
The drive automatically calculates this value when Auto-Tuning completes successfully. If you cannot do Auto-
Tuning, get the test report from the motor manufacturer. To calculate the motor line-to-line resistance, use the
information shown on the motor nameplate with one of these formulas:
E-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
B-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
F-type insulation: the resistance value (Ω) shown on the test report at 115 °C × 0.87
E4-06: Motor 2 Leakage Inductance
No.
(Hex.)
Name Description
Default
(Range)
E4-06
(0326)
Motor 2 Leakage Inductance
Sets the voltage drop from motor 2 leakage inductance as a percentage of Motor Rated Voltage when
motor 2 operates at the rated frequency and rated current.
Determined by o2-04, C6-01
(0.0 - 60.0%)
The drive sets this parameter during Rotational Auto-Tuning and Stationary Auto-Tuning.
Note:
You cannot usually find the quantity of voltage drop on the motor nameplate. If you do not know the value of the motor 2 leakage
inductance, get the test report from the motor manufacturer.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA500 series

Related product manuals