2.8 H: Terminal Function Selection
294 YASKAWA TOEPYAIGA5002A GA500 Programming
If the terminal is deactivated, the drive restarts acceleration and deceleration.
When the acceleration/deceleration ramp hold terminal is activated and d4-01 = 1 [Freq Reference Retention Select =
Enabled], the drive will store the output frequency in memory. While the acceleration/deceleration ramp hold
command is activated, the drive will always restart the motor at this output frequency.
Note:
Refer to d4-01: Freq Reference Hold Selection on page 234 for more information.
B: Overheat Alarm (oH2)
Setting Value Function Description
B Overheat Alarm (oH2)
Sets the drive to display an oH2 [Drive Overheat Warning] alarm when the input terminal is ON. The alarm does not have an effect
on drive operation.
C: Analog Terminal Enable Selection
Setting Value Function Description
C Analog Terminal Enable
Selection
Sets the command that enables or disables the terminals selected in H3-14 [Analog Input Terminal Enable Sel].
ON : Terminal selected with H3-14 is enabled
OFF : Terminal selected with H3-14 is disabled
E: ASR Integral Reset
Setting Value Function Description
E ASR Integral Reset
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
F: Not Used
Setting Value Function Description
F Not Used
Use this setting for unused terminals or to use terminals in through mode.
Through Mode uses the signal input to the terminal as a digital input for the upper sequence through a communication
option or MEMOBUS/Modbus communications. This input signal does not have an effect on drive operation.
10: Up Command
Setting Value Function Description
10 Up Command
Sets the command to use a push button switch to increase the drive frequency reference. You must also set Setting 11 [Down
Command].
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV