Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 Programming 325
OFF : The output frequency is less than the value of “L4-03 - L4-04,” or it is not more than the value
of L4-03.
Figure 2.82 Example of Frequency Detection 4 (value of L4-03 Is Positive)
■ 17: Torque Detection 1 (N.C.)
Setting Value Function Description
17 Torque Detection 1 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque is more than L6-02 [Torque Detection Level 1], or the level is less
than L6-02 for longer thanL6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than L6-02 for longer than L6-03.
• Refer to L6: Torque Detection on page 389 for more information.
■ 18: Torque Detection 2 (N.O.)
Setting Value Function Description
18 Torque Detection 2 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
Use the L6 [Torque Detection] parameters to set torque detection.
ON : The output current/torque is more than L6-05 [Torque Detection Level 2], or the level is less
than L6-05 for longer thanL6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than L6-05 for longer than L6-06.
• Refer to L6: Torque Detection on page 389 for more information.
■ 19: Torque Detection 2 (N.C.)
Setting Value Function Description
19 Torque Detection 2 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque is more than L6-05 [Torque Detection Level 2], or the level is less
than L6-05 for longer than L6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than L6-05 for longer than L6-06.
• Refer to L6: Torque Detection on page 389 for more information.
■ 1A: During Reverse
Setting Value Function Description
1A During reverse
The terminal activates when the motor operates in the reverse direction.