Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 Programming 327
Note:
Refer to L8-02: Overheat Alarm Level for more information.
21: Safe Torque OFF
Setting Value Function Description
21 Safe Torque OFF
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and when
terminals H1-HC and H2-HC are OFF (Open).
Note:
EDM = External Device Monitor
ON : Safety stop state
Terminals H1-HC and H2-HC are OFF (Open) (safety stop state).
OFF : Safety circuit fault or RUN/READY
Terminal H1-HC or terminal H2-HC is OFF (Open) (safety circuit fault), or the two terminals are ON or have short
circuited (RUN/READY).
22: Mechanical Weakening Detection
Setting Value Function Description
22 Mechanical Weakening
Detection
The terminal activates when the drive detects mechanical weakening.
Note:
Refer to Mechanical Weakening Detection Function for more information.
2F: Maintenance Notification
Setting Value Function Description
2F Maintenance Notification
The terminal activates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
IGBT
Cooling fan
Capacitor
Soft charge bypass relay
Note:
Refer to Alarm Outputs for Maintenance Monitors for more information.
30: During Torque Limit
Setting Value Function Description
30 During Torque Limit
The terminal activates when the torque reference is the torque limit set with L7 parameters or H3-02 or H3-10 [MFAI Function
Selection].
Note:
Refer to L7: Torque Limit on page 394 for more information.
37: During Frequency Output
Setting Value Function Description
37 During Frequency Output
The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV