2.9 L: Protection Functions
358 YASKAWA TOEPYAIGA5002A GA500 Programming
Figure 2.104 Connect Motor to PTC Thermistor Input
2. Set drive DIP switch S1-3 to V (voltage).
3. Set these MFAI terminals:
H3-09 = 0 [Terminal A2 Signal Level Select = 0-10V (LowLim=0)].
H3-10 = E [Terminal A2 Function Selection = Motor Temperature (PTC input)].
4. Set these L1 parameters:
L1-03 [Motor Thermistor oH Alarm Select]
L1-04 [Motor Thermistor oH Fault Select]
L1-05 [Motor Thermistor Filter Time]
L1-01: Motor Overload (oL1) Protection
No.
(Hex.)
Name Description
Default
(Range)
L1-01
(0480)
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors.
Determined by A1-02
(0 - 6)
This parameter enables and disables the motor overload protection with electronic thermal protectors.
The cooling capability of the motor changes when the speed control range of the motor changes. Use an electronic
thermal protector that aligns with the permitted load characteristics of the motor to select motor protection.
The electronic thermal protector of the drive uses these items to calculate motor overload tolerance and supply
overload protection for the motor:
Output Current
Output Frequency
Motor thermal characteristics
Time characteristics
If the drive detects motor overload, the drive will trigger an oL1 [Motor Overload] and stop the drive output.
Set H2-01 = 1F [Term MA/MB-MC Function Selection = Motor Overload Alarm (oL1)] to set a motor overload
alarm. If the motor overload level is more than 90% of the oL1 detection level, the output terminal activates and
triggers an overload alarm.
0 : Disabled
Disable motor protection when motor overload protection is not necessary or when the drive is operating more than
one motor.
Refer to Figure 2.105 for an example of the circuit configuration to connect more than one motor to one drive.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV