EasyManua.ls Logo

YASKAWA GA500 series - Page 380

YASKAWA GA500 series
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.9 L: Protection Functions
380 YASKAWA TOEPYAIGA5002A GA500 Programming
Figure 2.119 Stall Prevention Level during Run with Analog Input
L3-11: Overvoltage Suppression Select
No.
(Hex.)
Name Description
Default
(Range)
L3-11
(04C7)
Overvoltage Suppression
Select
Sets the overvoltage suppression function.
0
(0, 1)
0 : Disabled
The drive does not adjust the regenerative torque limit or the output frequency. If you apply a regenerative load, the
drive can detect an ov [Overvoltage] fault. Use this setting with a dynamic braking option.
1 : Enabled
When a regenerative load increases the DC bus voltage, the drive decreases the regenerative torque limit and
increases the output frequency to prevent ov
L3-17: DC Bus Regulation Level
No.
(Hex.)
Name Description
Default
(Range)
L3-17
(0462)
DC Bus Regulation Level
Sets the target value for the DC bus voltage when the overvoltage suppression function and the Decel
Stall Prevention function (Intelligent Stall Prevention) are active.
200 V Class: 375 V, 400 V:
750 V
(200 V Class: 150 to 400 V,
400 V Class: 300 to 800 V)
Note:
This value is initialized when E1-01 [Input AC Supply Voltage] is changed.
Sets this parameter for any of the following circumstances.
L3-11 = 1 [OV Suppression Function Select = Enabled].
L3-04 = 2 [Decel Stall Prevention Selection = Automatic Decel Reduction].
L3-20: DC Bus Voltage Adjustment Gain
No.
(Hex.)
Name Description
Default
(Range)
L3-20
(0465)
Expert
DC Bus Voltage Adjustment
Gain
Sets the proportional gain used to control the DC bus voltage.
Determined by A1-02
(0.00 - 5.00)
Set one of these parameters to enable L3-20:
L2-29 = 1 [KEB Method Selection = Single Drive KEB Ride-Thru 2]
L3-04 = 2 [Decel Stall Prevention Selection = Automatic Decel Reduction]
L3-11 = 1 [OV Suppression Function Select = Enabled]
H1-xx = 7A or 7B [MFDI Function Select = KEB Ride-Thru 2 (N.O./N.C.)]
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA500 series

Related product manuals