Parameter Details
2
2.10 n: Special Adjustment
YASKAWA TOEPYAIGA5002A GA500 Programming 423
n8-74: Light Load Iq Level
No.
(Hex.)
Name Description
Default
(Range)
n8-74
(05C3)
Expert
Light Load Iq Level
Set n8-48 [Pull-in/Light Load Id Current] to the percentage of load current (q-axis current) that you
will apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
30%
(0 - 255%)
Note:
If n8-74 > n8-75 [Medium Load Iq Level (low)], the drive will detect oPE08 [Parameter Selection Error].
The change is linear between n8-74 and n8-75 and the level of the pull-in current from n8-48 to n8-78 [Medium Load Id Current].
n8-75: Medium Load Iq Level (low)
No.
(Hex.)
Name Description
Default
(Range)
n8-75
(05C4)
Expert
Medium Load Iq Level (low)
Set n8-78 [Medium Load Id Current] to the percentage of load current (q-axis current) that you will
apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
50%
(0 - 255%)
Note:
If n8-74 [Light Load Iq Level] > n8-75, the drive will detect oPE08 [Parameter Selection Error].
The change is linear between n8-74 and n8-75 and the level of the pull-in current from n8-48 to n8-78 [Medium Load Id Current].
n8-76: Id Switching Filter Time
No.
(Hex.)
Name Description
Default
(Range)
n8-76
(05CD)
Expert
Id Switching Filter Time
Sets the filter time constant for the d-axis current reference. Usually it is not necessary to change this
setting.
200 ms
(0 - 5000)
n8-77: Heavy Load Iq Level
No.
(Hex.)
Name Description
Default
(Range)
n8-77
(05CE)
Expert
Heavy Load Iq Level
Set n8-49 [Heavy Load Id Current] to the percentage of load current (q-axis current) that you will
apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
90%
(0 - 255%)
Note:
The change is linear between n8-75 [Medium Load Iq Level (low)] and n8-77 and the level of the pull-in current from n8-78 [Medium Load
Id Current] to n8-49 [Heavy Load Id Current].
n8-78: Medium Load Id Current
No.
(Hex.)
Name Description
Default
(Range)
n8-78
(05F4)
RUN
Expert
Medium Load Id Current
Sets the level of the pull-in current as a percentage, where E5-03 [PM Motor Rated Current (FLA)] =
100%.
0%
(0 - 255%)
n8-79: Pull-in Current @ Deceleration
No.
(Hex.)
Name Description
Default
(Range)
n8-79
(05FE)
Pull-in Current @
Deceleration
Sets the pull-in current that can flow during deceleration as a percentage of the E5-03 [PM Motor
Rated Current (FLA)].
50%
(0 - 200%)
If overcurrent occurs during deceleration, slowly decrease the setting in 5% increments.
Note:
When n8-79 = 0, the drive will use the value set in n8-51 [Pull-in Current @ Acceleration].
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA500 series

Related product manuals