2.11 o: Keypad-Related Settings
YASKAWA TOEPYAIGA5002A GA500 Programming 427
A - Set Ux-xx [Monitors] (Monitor 1) to o1-24.
B - Set Ux-xx [Monitors] (Monitor 2) to o1-25.
C - Set the maximum value of Monitor 2 to o1-50.
D - Set the minimum value of Monitor 2 to o1-49.
E - Set the time scale to o1-51.
F - Set the minimum value of Monitor 1 to o1-47.
G - Set the maximum value of Monitor 1 to o1-48.
Figure 2.131 Trend Plot Display
o1-01: User Monitor Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-01
(0500)
RUN
User Monitor Selection
Sets the U monitor for the Drive Mode. This parameter is only available when you use an LED
keypad.
106
(104 - 855)
When the drive is in Drive Mode, push on the keypad to cycle through this data: frequency reference
rotational direction output frequency output current o1-01 selection.
Set the x-xx part of Ux-xx that is shown in the fifth position in Drive Mode. For example, to show U1-05 [Motor
Speed], set o1-01 = 105.
Note:
The monitors that you can select are different for different control methods.
o1-02: Monitor Selection at Power-up
No.
(Hex.)
Name Description
Default
(Range)
o1-02
(0501)
RUN
Monitor Selection at Power-
up
Sets the monitor item that the keypad screen shows after energizing the drive. Refer to U: Monitors
for information about the monitor items that the keypad screen can show. This parameter is only
available when you use an LED keypad.
1
(1 - 5)
1 : Frequency Reference (U1-01)
2 : Direction
3 : Output Frequency (U1-02)
4 : Output Current (U1-03)
5 : User Monitor (o1-01)
Shows the monitor item selected in o1-01 [User Monitor Selection].
o1-03: Frequency Display Unit Selection
No.
(Hex.)
Name Description
Default
(Setting Range)
o1-03
(0502)
Frequency Display Unit
Selection
Sets the display units for the frequency reference and output frequency.
Determined by A1-02
(0 - 3)
G
F
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV