2.11 o: Keypad-Related Settings
436 YASKAWA TOEPYAIGA5002A GA500 Programming
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is not
necessary to push . The drive keeps the frequency reference for 5 seconds after you use and on the
keypad to change the frequency reference value.
o2-06: Keypad Disconnect Detection
No.
(Hex.)
Name Description
Default
(Range)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
1
(0, 1)
This parameter continues to operate if the keypad installed to the drive becomes disconnected.
This parameter is enabled in these conditions:
When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
In LOCAL Mode
0 : Disabled
The drive continues operation when it detects a keypad disconnection.
1 : Enabled
The drive stops operation, detects oPr [Keypad Connection Fault], and the motor coasts to stop when the drive
detects a keypad disconnection.
o2-07: Keypad RUN Direction @ Power-up
No.
(Hex.)
Name Description
Default
(Range)
o2-07
(0527)
Keypad RUN Direction @
Power-up
Sets the direction of motor rotation when the drive is energized and the keypad is the Run command
source.
0
(0, 1)
This parameter is enabled in these conditions:
When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
In LOCAL Mode
0 : Forward
1 : Reverse
o2-09: Region Code
No.
(Hex.)
Name Description
Default
(Range)
o2-09
(050D)
Reserved - -
o2-19: Parameter Write during Uv
No.
(Hex.)
Name Description
Default
(Range)
o2-19
(061F)
Expert
Parameter Write during Uv
Lets you change parameters during Uv [Undervoltage].
0
( 0, 1 )
0 : Disable
1 : Enabled
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV