Parameter Details
2
2.11 o: Keypad-Related Settings
YASKAWA TOEPYAIGA5002A GA500 Programming 445
No. Item
Number of
Characters
Description
15 Encoding data 4 Log Monitor Data 1 to 10 Code Data (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 1 through 10. A bit value of 1 shows that the data represents a
negative value. (Log monitor data 1 through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have values of 1, and the encoding data
= 0010010010 (Bin.) = 0092 (Hex.)
16 Row number 6 Row number (Hex.) in the data log file
o5-01: Log Start/Stop Selection
No.
(Hex.)
Name Description
Default
(Range)
o5-01
(1551)
RUN
Log Start/Stop Selection
Sets the data log function. This parameter is only available when using an LCD keypad.
0
(0 - 1)
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
o5-02: Log Sampling Interval
No.
(Hex.)
Name Description
Default
(Range)
o5-02
(1552)
RUN
Log Sampling Interval
Sets the data log sampling cycle. This parameter is only available when using an LCD keypad.
100 ms
(100 - 60000 ms)
o5-03: Log Monitor Data 1
No.
(Hex.)
Name Description
Default
(Range)
o5-03
(1553)
RUN
Log Monitor Data 1
Sets the data log monitor. This parameter is only available when using an LCD keypad.
101
(000, 101 - 999)
Note:
Set the number of the U monitor to record the data log.
For example, to show U1-01 [Frequency Reference], set o5-03 = 101. When it is not necessary to set data log monitors, set this parameter to
000. You cannot set U2 monitor [Fault Trace] or U3 Monitor [Fault History].
o5-04: Log Monitor Data 2
No.
(Hex.)
Name Description
Default
(Range)
o5-04
(1554)
RUN
Log Monitor Data 2
Sets the data log monitor. This parameter is only available when using an LCD keypad.
102
(000, 101 - 999)
Note:
Set the U monitor number you will log.
For example, to show U1-02 [Output Frequency], set o5-04 = 102. When it is not necessary to set data log monitor, set this parameter to
000.
o5-05: Log Monitor Data 3
No.
(Hex.)
Name Description
Default
(Range)
o5-05
(1555)
RUN
Log Monitor Data 3
Sets the data log monitor. This parameter is only available when using an LCD keypad.
103
(000, 101 - 999)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV