1.10 H: Terminal Functions
64 YASKAWA TOEPYAIGA5002A GA500 Programming
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H5-05
(0429)
Comm Fault Detection
Selection
Sets the function that detects CE [Modbus Communication Error] issues during
MEMOBUS/Modbus communications.
0 : Disabled
1 : Enabled
1
(0, 1)
346
H5-06
(042A)
Drive Transmit Wait
Time
Sets the time to wait to send a response message after the drive receives a command
message from the master.
Note:
Restart the drive after changing the parameter setting.
5 ms
(0 - 65 ms)
347
H5-09
(0435)
CE Detection Time
Sets the detection time for CE [Modbus Communication Error] issues when
communication stops.
2.0 s
(0.0 - 25.0 s)
347
H5-10
(0436)
Modbus Register 0025H
Unit Sel
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor
register 0025H (output voltage reference monitor).
0 : 0.1 V units
1 : 1 V units
0
(0, 1)
347
H5-11
(043C)
RUN
Comm ENTER
Command Mode
Sets the function to make the Enter command necessary to change parameters through
MEMOBUS/Modbus communications.
0 : ENTER Command Required
1 : ENTER Command Not Required
1
(0, 1)
347
H5-12
(043D)
Run Command Method
Selection
Sets the input method for the Run command when b1-02 = 2 [Run Command Selection 1 =
Memobus/Modbus Communications] or b1-16 = 2 [Run Command Selection 2 =
Memobus/Modbus Communications].
0 : FWD/Stop, REV/Stop
1 : Run/Stop, FWD/REV
0
(0, 1)
347
H5-17
(11A1)
Expert
ENTER command
response @CPU BUSY
Sets operation when the EEPROM write command is sent without EEPROM write
available. Usually it is not necessary to change this setting.
0 : Ignore Command(No ROM/RAM Write)
1 : Write to RAM Only
0
(0, 1)
348
H5-18
(11A2)
Motor Speed Filter over
Comms
Sets the filter time constant used when monitoring motor speed during MEMOBUS/
Modbus communications or with a communication option.
0 ms
(0 - 100 ms)
348
H5-20
(0B57)
Communication
Parameters Reload
Sets the function to immediately enable updated MEMOBUS/Modbus communications
parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
0
(0, 1)
348
H5-22
(11CF)
Speed Search from
MODBUS
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of
15DFH).
0 : Disabled
1 : Enabled
0
(0, 1)
348
H5-25
(1589)
RUN
Function 5A Register 1
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0044H (U1-05)
(0000H - FFFFH)
349
H5-26
(158A)
RUN
Function 5A Register 2
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0045H (U1-06)
(0000H - FFFFH)
349
H5-27
(158B)
RUN
Function 5A Register 3
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0042H (U1-03)
(0000H - FFFFH)
349
H5-28
(158C)
RUN
Function 5A Register 4
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0049H (U1-10)
(0000H - FFFFH)
349
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV