No. Parameter Name Setting Range Default
E2-01 Motor Rated Current
10% to 200% of the drive
rated current
Determined by
o2-04
Note: 1. The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the
drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW. Refer to Power Ratings on page 234 for details.
2. An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly
to prevent this error.
n
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No. Parameter Name Setting Range Default
E2-04 Number of Motor Poles 2 to 48 2
n
H1-01 to H1-08: Functions for Terminals S1 to S8
These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in Table
4.20.
No. Parameter Name
Setting
Range
Default
H1-01 Multi-Function Digital Input Terminal S1 Function Selection 1 to 9F
40 (F)
<1>
: Forward Run Command (2-Wire sequence)
H1-02 Multi-Function Digital Input Terminal S2 Function Selection 1 to 9F F: Through Mode
H1-03 Multi-Function Digital Input Terminal S3 Function Selection 0 to 9F 26: External Pump Fault
H1-04 Multi-Function Digital Input Terminal S4 Function Selection 0 to 9F 14: Fault Reset
H1-05 Multi-Function Digital Input Terminal S5 Function Selection 0 to 9F
8D (0)
<1>
: Multi Setpoint 1
H1-06 Multi-Function Digital Input Terminal S6 Function Selection 0 to 9F
80 (3)
<1>
: HAND Mode
H1-07 Multi-Function Digital Input Terminal S7 Function Selection 0 to 9F
81 (4)
<1>
: HAND Mode 2
H1-08 Multi-Function Digital Input Terminal S8 Function Selection 0 to 9F
F (6)
<1>
: Through Mode
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Table 4.20 Multi-Function Digital Input Terminal Settings
Setting Function Page
0 3-Wire sequence
3 Multi-Step Speed Reference 1
4 Multi-Step Speed Reference 2
5 Multi-Step Speed Reference 3
6 Jog reference selection
7 Accel/decel time selection 1
8 Baseblock command (N.O.)
9 Baseblock command (N.C.)
A Accel/decel ramp hold
B Drive overheat alarm (oH2)
C Analog terminal input selection
F Through mode
10 Up command
11 Down command
12 Forward Jog
13 Reverse Jog
14 Fault reset
15 Fast Stop (N.O.)
17 Fast Stop (N.C.)
18 Timer function input
19 PID disable
Setting Function Page
1A Accel/decel time selection 2
1B Program lockout
1E Reference sample hold
20 to 2F Ext. pump fault
30 PID integral reset
31 PID integral hold
32
Multi-Step Speed
Reference 4
34 PID soft starter cancel
35 PID input level selection
40
Forward run command
(2-Wire sequence)
41
Reverse run command
(2-Wire sequence)
42
Run command
(2-Wire sequence 2)
43
FWD/REV command
(2-Wire sequence 2)
47 Node setup
51 Sequence Timer Disable
52 Sequence Timer Cancel
60 DC Injection Braking command
4.6 Basic iQpump Setup and Application Preset Parameters
158
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide