12 Error Lists
12-10
A.C51:
Overtravel Detection at
Pole Detection
An overtravel signal was detected
during polarity detection.
Check the position after
overtravel.
Perform the wiring for an
overtravel signal. Exe-
cute polarity detection at a
position where an over-
travel signal is not
detected.
A.C52:
Pole Detection Uncom-
pleted
The servo has been turned ON under
the following circumstances.
An absolute linear scale is being
used.
The polarity detection selection for
the absolute linear scale was set to
not execute. (Pn587.0 = 0)
Polarity was not yet detected
-
When using an absolute
linear scale, set the
parameter Pn587.0 to 1 to
execute polarity detection.
A.C53:
Out of Range for Pole
Detection
The movement distance exceeded the
set value of Pn48E in the middle of
detection.
-
Increase the value of the
polarity detection range
(Pn48E). Or, increase the
polarity detection speed
loop gain (Pn481).
A.C54:
Pole Detection Error 2
External force was applied to the lin-
ear servomotor.
-
Increase the value of the
polarity detection confir-
mation force reference
(Pn495).
Increase the value of the
polarity detection allow-
able error range (Pn498).
(Note that increasing the
allowable error range will
also increase the motor
temperature.)
Alarm Number: Alarm
Name (Alarm
Description)
Cause Investigative Actions Corrective Actions