EasyManuals Logo

YASKAWA Varispeed G7 User Manual

YASKAWA Varispeed G7
499 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #195 background imageLoading...
Page #195 background image
5-82
U1-36
PID input
volume
PID feedback volume
Given as maximum frequency/
100%
10 V: Max. frequency
(-10 to 10 V possible)
0.01
%
AAAAA63H
PID Input
U1-37
PID output
volume
PID control output
Given as maximum frequency/
100%
10 V: Max. frequency
(-10 to 10 V possible)
0.01
%
AAAAA64H
PID Output
U1-38
PID target
value
PID target value
Given as maximum frequency/
100%
10 V: Max. frequency
0.01
%
AAAAA65H
PID Set-
point
U1-39
MEMOBUS
communi-
cations
error code
Shows MEMOBUS errors.
(Cannot be output.) - A A A A A 66H
Transmit
Err
U1-40
Cooling fan
operating
time
Monitors the total operating
time of the cooling fan. The
time can be set in 02-10.
(Cannot be output.)
1
hr
AAAAA68H
FAN
Elapsed
Time
U1-42
Estimated
motor flux
Monitors the calculated value
of the motor flux. 100% is dis-
played for the rated motor
flux.
10 V: Rated motor flux
0.1
%
No No No No A 69H
Mot Flux
EST
U1-43
Motor flux
current
compensa-
tion
Monitors motor flux current
compensation value. 100% is
displayed for the rated second-
ary current of the motor.
10 V: Rated secondary cur-
rent of motor
(-10 V to 10 V)
0.1
%
No No No No A 6AH
Id Comp
Value
U1-44
ASR out-
put without
filter
Monitors the output from the
speed control loop (i.e., the
primary filter input value).
100% is displayed for rated
secondary current of the
motor.
10 V: Rated secondary cur-
rent of motor
(-10 V to 10 V)
0.01
%
No No No A A 6BH
ASR Out-
put w Fil
U1-45
Feed for-
ward con-
trol output
Monitors the output from feed
forward control. 100% is dis-
played for rated secondary
current of the motor.
10 V: Rated secondary cur-
rent of motor
(-10 V to 10 V)
0.01
%
No No No A A 6CH
FF Cout
Output
Con-
stant
Number
Name
Description
Output Signal Level
During Multi-Function
Analog Output
Min.
Unit
Control Methods
MEMO-
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
1: CRC error
1: Data length error
Not used (always 0).
1: Parity
error
1: Overrun
error
1: Framing
error
1:
Timeout
Not used (always 0).
U1-39= 00000000

Table of Contents

Other manuals for YASKAWA Varispeed G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 and is the answer not in the manual?

YASKAWA Varispeed G7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7
CategoryInverter
LanguageEnglish

Related product manuals