EasyManua.ls Logo

YASKAWA Varispeed G7 - Page 492

YASKAWA Varispeed G7
499 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-36
Table 10.7 User Constants (Continued)
* 1. Not initialized. (Japanese standard specifications: A1-00 = 1, A1-02 = 2)
* 2. When the control method is changed, the factory setting will change. The open-loop vector 1 factory settings are given.
* 3. The factory setting is 1.0 when using flux vector control.
* 4. The factory setting is 2.00 s when Inverter capacity is 55 kW min.
The factory setting will change when the control method is changed. The open-loop vector 1 factory setting is given.
* 5. By setting E2-11 (Motor rated output) the appropriate value will be set.
* 6. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter of 0.4 kW are given.
* 7. When the control method is changed, the factory settings will change. The flux vector factory settings are given.
* 8. This constant can be monitored or set only when F is set for C6-02.
* 9. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 10.E1-11 and E1-12 are disregarded when set to 0.0.
* 11.E1-13 is set to the same value as E1-05 by autotuning.
* 12.The same capacity as that of the Inverter will be set if the constants are initialized.
* 13.Applicable for G7-Series Inverters with software versions PRG: 1038 and later. Refer to MECHATROLINK COMMUNICATIONS INTERFACE CARD
INSTRUCTIONS (TOBPC73060008) for details.
* 14.The factory settings in the parentheses are for 3-wire sequence.
N4-32
Speed estimator gain fluctuation
frequency 1
5.0
N4-33
Speed estimator gain fluctuation
frequency 2
20.0
N4-34
Speed estimator gain fluctuation
rate
200.0
N5-01 Feed forward control selection
0
*7
N5-02 Motor acceleration time
0.178
*6
N5-03 Feed forward proportional gain 1.0
o1-01 Monitor selection 6
o1-02 Monitor selection after power up 1
o1-03
Frequency units of reference set-
ting and monitor
0
o1-04
Setting unit for frequency con-
stants related to V/f characteristics
0
o1-05 LCD brightness adjustment 3
o2-01
LOCAL/REMOTE key enable/dis-
able
1
o2-02
STOP key during control circuit
terminal operation
1
o2-03 User constant initial value 0
o2-04 kVA selection
0
*6
o2-05
Frequency reference setting
method selection
0
o2-06
Operation selection when digital
operator is disconnected
0
o2-07 Cumulative operation time setting 0
No. Name
Fac-
tory
Setting
Set-
ting
o2-08
Cumulative operation time selec-
tion
0
o2-10 Fan operation time setting 0
o2-12
Fault trace/fault history clear func-
tion
0
o2-14
Output power monitor clear selec-
tion
0
o2-18
*18
Capacitor maintenance setting 0
o3-01 Copy function selection 0
o3-02 Read permitted selection 0
T1-00 Motor 1/2 selection 1
T1-01 Autotuning mode selection
0
*2
T1-02 Motor output power
0.40
*6
T1-03 Motor rated voltage
200.0
*9
T1-04 Motor rated current
1.90
*6
T1-05 Motor base frequency 60.0
T1-06 Number of motor poles 4
T1-07 Motor base speed 1750
T1-08
PG pulses per revolution for teach-
ing
600
T1-09
*18
Motor no-load current
1.20
*6
No. Name
Fac-
tory
Setting
Set-
ting

Table of Contents

Other manuals for YASKAWA Varispeed G7

Related product manuals