EasyManua.ls Logo

YOKOGAWA GX20

YOKOGAWA GX20
707 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-36
IM 04L51B01-01EN
Program Operation Status
Data Register Description Data Type
Program operation status 308101 1: Program operation stop,
operation end
2: Program running
16-bit signed integer
Running pattern number
display
308102 1 to 99
Running segment number
display
308103 1 to 99
0: Program stopped
Wait state 308104 0: Not waiting
1: Waiting
Remaining segment time of
the running pattern (hours:
0 to 99)
308105 0 to 99 (hours)
Remaining segment time
of the running pattern
(minutes: 0 to 59)
308106 0 to 59 (minutes)
Remaining segment time
of the running pattern
(seconds: 0 to 59)
308107 0 to 59 (s)
PV event status 308111
|
308142
0: Event absent
1: Event present
Time event status 308151
|
308182
0: Event absent
1: Event present
4.5 Modbus Function and Register Assignments

Table of Contents

Related product manuals