4-58
IM 04L51B01-01EN
Data Hold
Register
Supplementary Information Data Type
Write a message
(free message)
409230 0: Fixed at 0 when reading
UTF-8 characters (2
characters)
Up to 35 characters
(except the number of valid
characters is 32)
Ignored for preset messages
Attach a terminator at the
end
16-bit signed integer
Batch, lot number 409301 Lower bytes of the lot
number
32-bit signed integer
409302 Higher bytes of the lot
number
409303 Batch number
UTF-8 characters (2
characters)
Up to 32 characters [attach
the terminator '\0' at the end]
16-bit signed integer
| |
409319 Batch number
UTF-8 characters (2
characters)
Up to 32 characters [attach
the terminator '\0' at the end]
Batch, lot number (multi
batch support)
409351 1 or greater: Batch group
number
When reading, the batch
group number that performed
writing previously
Default value: 0
16-bit signed integer
409352 Lower bytes of the lot
number
When reading, the lot
number corresponding to the
above batch group number
0 if there is no corresponding
batch group number
32-bit signed integer
409353 Higher bytes of the lot
number
When reading, the lot
number corresponding to the
above batch group number
0 if there is no corresponding
batch group number
Batch, lot number (multi
batch support)
409354 Batch number
UTF-8 characters (2
characters)
Up to 32 characters [attach
the terminator '\0' at the end]
When reading, the batch
number corresponding to the
above batch group number
NULL character if there is no
corresponding batch group
number
16-bit signed integer
| |
409379 Batch number
UTF-8 characters (2
characters)
Up to 32 characters [attach
the terminator '\0' at the end]
When reading, the batch
number corresponding to the
above batch group number
NULL character if there is no
corresponding batch group
number
Continued on next page
4.5 Modbus Function and Register Assignments