• Powerconsumption:
Supply
voltage
LCDbacklight
off
Normal
operation
Maximum
12VDC 7VA 10VA 26VA
Isolation
• Insulationresistance:BetweentheEthernet,
RS-422/485,andeachinsulationterminalsand
earth:20MΩorgreaterat500VDC
• Withstandvoltage:
Betweenthepowerterminalandearth(Incase
ofPowersupplysufxcode:1):3000VACat
50/60Hzforoneminute
Betweenthepowerterminalandearth(Incase
ofPowersupplysufxcode:2):500VACat
50/60Hzforoneminute
Betweenthecontactoutputterminalandearth:
3000VACat50/60Hzforoneminute
Betweentheinput/outputmodulesandearth:
DependsonthespecicationofI/Omodule.
• Grounding:Besuretosetalowgrounding
resistance.
• Isolation:
Power terminal
The circuits divided by lines are insulated mutually.
Internal circuit
FAIL output terminal
Ethernet port
RS-422/485 terminal
Input and output module terminal
Input and output module internal circuit
Earth (PE) terminal
RS-232 terminal
SD card slot
USB port
SafetyandEMCStandards
• CSA:
CAN/CSA22.2 No.61010.1, installation category
II(*1),andpollutiondegree2(*2)
CAN/CSA-C22.2 NO. 61010-2-030
CAN/CSA-IEC61010-201
*4
• UL:UL61010-1,UL61010-2-030(CSANRTL/C)
UL61010-2-201(CSANRTL/C)
• CE/EMCdirective:
EN61326-1compliance,ClassATable2
EN61000-3-2compliance
EN61000-3-3compliance
EN55011 Class A Group 1
• CE/Lowvoltagedirective:
EN61010-1, EN 61010-2-030
InstallationcategoryII
*1
Pollution degree 2
*2
Measurementcategory
*3
EN61010-2-201
*4
• C-Tick:EN55011compliance,ClassAGroup1
• KCmarking:Electromagneticwaveinterference
preventionstandard,electromagneticwave
protectionstandardcompliance
*1 Installationcategory(overvoltagecategory)II:
Describesanumberwhichdenesatransient
overvoltagecondition.
Impliestheregulationforimpulsewithstand
voltage.
“II”appliestoelectricalequipmentwhich
issuppliedfromthexedinstallationlikea
distribution board.
*2 Pollution degree 2:
Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or
surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.
Normally,onlynon-conductivepollutionoccurs.
*3 Measurementcategory:Dependsonthe
specicationofeachmodules
*4 Thisproductisdesignedasopenequipment
undertherelevantstandard,installitasfollows:
•TomaketheGP10/GP20complywiththe
relevantstandard,supportthepartsofthedevice
otherthanthefront-panelcontrolareawithan
instrumentationpanelorthelike,andinstallitina
locationwherepeoplecannottouchtheterminals
carelessly or in a panel.
•InstalltheGX60/GMunitinapanelwithadoor.
•Theinstrumentationpanelorpanelusedfor
supportmustcomplywithCSA/UL/EN61010-
2-201ormustbeatleastIP1X(degreesof
protection)andatleastIK09.
Category Measurement
category
Description Remarks
II CATII
Availableinthetesting
andmeasuringcircuits
directly connected
to a usage location
(receptacle or the like)
ofalow-voltagemain
powersupplyfacility.
Appliances,
portable
equipment,
etc.
III CATIII
Availableinthetesting
andmeasuringcircuits
connected to a power
distributionportionof
alow-voltagemain
powersupplyfacility.
Distribution
board, circuit
breaker, etc.
IV CATIV
Availableinthetesting
andmeasuringcircuits
connected to a power
sourceofalow-
voltagemainpower
supplyfacility.
verhead
wire, cable
systems,etc.
• WEEEDirective:Compliant
NormalOperatingConditions:
• Powersupplyvoltage:100to240VAC±10%
• Powersupplyfrequency:50/60Hz±2%
• Ambienttemperature:0to50°C
• Ambienthumidity:20to80%RH(at5to40°C)
(no condensation)
• Magneticeld:400A/morless(DCand50/60
Hz)
• Vibration:
5≤f<8.4Hzamplitude3.5mm(peak)
8.4≤f≤160Hzacceleration9.8m/s
2
• Shock:
Non-energization,500m/s
2
orless,approximate
10ms,6directions(±X,±Y,±Z),3timesineach
direction
• Mountingposition:Canbeinclinedupto30
degreesbackward.Leftandrighthorizontal
wheninstallingthepanelmountandwallmount.
• Altitude:2000morless
• Installationlocation:Indoors
• Warm-uptime:Atleast30minutesafterpower
on