GS 04L53B01-31EN
15
All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation 2017.06.26-00
• Program screen display:
Program operation status display screen:
displaystheprogramoperatingstatusandthe
current PV simultaneously (GX/GP only)
Numberofdisplayloops:20max.
Numberofscreens:1
Display update interval:
Digitaldisplayarea:500msxed
Trenddisplayarea:accordingtothe
trend interval
Programeventdisplay:possible
ProgramOperationScreen
Theprogramoperationscreenisfordisplayingthe
programpatternthatiscurrentlyrunning.
•Otherrecorderoperations:
Saveeachprogrampatterntole
Load program patterns
Delete program patterns
ControlDataAcquisition/Recording
Function(GX/GP/GMrecorder
function)
• Acquires/records control data (PV, SP, OUT, etc.)
Acquisition/recordingispossiblebyinstallingaPID
ControlModuleandreconguringthesystem.
PIDchanneldatacanbeusedasanI/Ochannelto
besavedindatalesorusedincomputationand
reports.
•Controloperationsummary(numberofsavedles:up
to3000datavalues,numberofdisplaydatavalues:
up 1000 data values)
•Controlalarmsummary(numberofsavedles:upto
1000,numberofdisplaydataentries:up500)
InstallationConditions
SystematicPIDControlModuleLimitations
GX/GP/GMsystem
(Standardtype)
Max.3devices
GX/GP/GMsystem
(Largememorytype)
Max.10devices
However,ifthesystemincludesPIDcontrol
modules (GX90UT), digital output modules
(GX90YD), and digital input/output modules
(GX90WD),themaximumtotalnumberofthese
modules is 10.
Iftherecorder’smeasurementoperationmodeishigh
speed or dual interval, PID control modules will not
work.(Fordetails,seethegeneralspecicationsof
theGX/GP/GMrecorder.)
Input/OutputModuleLimitationsonRecorders
andUnitsWhenUsingthePIDControlModule
GX10/GP10recorder
(Standardtype)
Max.3devices*
Note:
GX20/GP20recorder
(Standardtype)
Max.8devices*
GX20/GP20recorder
(Largememorytype)
Max.8devices*
GMsingleunit
conguration,main
(standardtype)
Max.5devices*
GMsingleunit
conguration,main(large
memorytype)
Max.5devices*
GMmultiunitconguration,
main(standardtype)
Max.5devices*
GMmultiunitconguration,
main(largememorytype)
Max.5devices*
GX60expandableI/O Installablewithinthe
system limitations
GMmultiunitconguration,
subunit
Installablewithinthe
system limitations
* Thisisthenumberofdevicesincludingthe
expansionmodules(GX90EX)installedintheGX/
GP/GMrecorderwhenanexpandableI/Ounit
(GX60)orGMsubunitisused.
Note:Themaximumnumberis2whentheGP10
supply voltage is 12 VDC.