EasyManua.ls Logo

York OPTIVIEW YK - Program Switches

York OPTIVIEW YK
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
65
SECTION 4 - MICROBOARD 031-02430-000 AND 031-02430-001
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS JCI COMPANY CONFIDENTIAL
4
JP13 – Watchdog Enable/Disable. Soldered wire
jumper.
Never disable the watchdog protection.
Severe compressor or chiller damage
could result. The ability to disable the
watchdog protection is provided for fac-
tory testing only.
IN: – Watchdog enabled.
OUT: – Watchdog disabled.
JP14 – BRAM size (Microboard 031-02430-001 only)
– Must be positioned according to the size of
the BRAM installed on the board.
IN: 32K (BRAM 031-02431-000).
OUT: 128K (BRAM 031-02565-000).
(For 031-02430-000 Microboards, this is a
non-removable wire jumper soldered in place
at time the board is manufactured. It must NOT
beremovedbyeldservicepersonnel.
JP16 – Not Used.
JP17 – COM 2 Serial Port Mode (Microboard 031-
02430-001 only). This port can operate in ei-
ther RS-232 or RS-485 Mode, depending on
the position of this jumper.
PINS 1-2: RS-485 (required for MV SSS, MV
VSD and those Variable Speed Drives and
Style B Liquid Cooled Solid State Starters that
communicate with the microboard using Mod-
bus protocol.
PINS 2-3: RS-232 (not used).
JP21 –Factory mounted thermal-type ow sensor –
evaporator.
Pins 1-2: Not Used.
Pins 2-3: Factory mounted evaporator Ther-
maltypeowsensor(newproductionchillers
before June 2009) or Leaving Chilled Liquid
Temperature Thermistor (chillers equipped
with the optional Heat Pump Duty feature).
JP22 –Factory mounted thermal-type ow sensor –
condenser.
Pins 1-2: Not Used.
Pins 2-3: Factory mounted condenser Thermal
type owsensor(new production chillers be-
fore June 2009).
JP23 – Remote Current Limit setpoint (J22) type. Con-
guresAnalogInputfor0to10VDC,2to10
VDC, 0 to 20mA or 4 to 20mA.
OUT: Allows 0 to 10 VDC or 2 to 10 VDC in-
put on J22-1.
Pins 1-2: Allows a 0 to 20mA or 4 to 20mA
input on J22-2.
Pins 2-3: Not used.
JP24 – Remote Leaving Chilled Liquid Temperature
setpoint(J22)type.ConguresAnalogInputfor
0 to 10 VDC, 2 to 10 VDC, 0 to 20mA or 4 to
20mA.
OUT: Allows 0 to 10 VDC or 2 to 10 VDC in-
put on J22-3.
Pins 1-2: Allows a 0 to 20mA or 4 to 20mA
input on J22-4.
Pins 2-3: Not used.
JP25 – DC Undervoltage signal for Proximity Probe.
Pins 1-2: Correct position for YK
Pins 2-3: Not Used
JP27 –COM4serialcommunicationsport.Congures
COM 4 port for either RS-485 (COM 4A) or
RS-232 for E-Link Gateway board (COM4B).
Pins 1-2: Enables port 4A. Allows an RS-485
connection to Microboard J11. Not used.
Pins 2-3: Enables port 4B. Allows an RS-232
connection to Microboard J2 for E-Link Gate-
way communications.
PROGRAM SWITCHES
SW1-1 – Refrigerant Selection. Must be set according
to the refrigerant type installed in chiller.
ON – R-134a
OFF R22
SW1-2 – Liquid Type. Must be set according to whether
the chiller is cooling water or brine solution.
ON – Brine. Leaving Chilled setpoint range is
10°F to 70°F.
OFF Water. Leaving Chilled setpoint range
38°F (36°F if Smart Freeze enabled) to 70°F.
SW1-3 – Diagnostics. Enables or Disables the soft-
ware diagnostics. See SECTION 34 - DIAG-
NOSTICS AND TROUBLESHOOTING of
this manual.
ON – Enables diagnostics. Disables normal
chiller operation.
OFF Disables diagnostics. Enables normal
chiller operation.
SW1-4 – Not used.

Table of Contents

Related product manuals