23
SECTION 2 - SYSTEM ARCHITECTURE
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS JCI COMPANY CONFIDENTIAL
2
FIGURE 2 - OPTIVIEW CONTROL CENTER - MOD A SOLID STATE STARTER APPLICATIONS
LD09037c
DIGITAL
IN
TRIAC
OUT
RELAY
OUT
POWER
SUPPLY
MICROBOARD
I / O BOARD
KEYPAD
DISPLAY
INTERFACE
BOARD
LIQUID
CRYSTAL
DISPLAY
LAMP
BACKLIGHT
INVERTER
BOARD
LAMP
CONTROL
ROW IN
COLUMN OUT
DISPLAY DATA
VANE MOTOR SWITCH
REMOTE CYCLING
HIGH PRESSURE SAFETY
LOCAL START / STOP SWITCH
CHILLED AND CONDENSER WATER FLOW SWITCHES
OIL PUMP VSD CYCLING STATUS
MOTOR CONTROLLER SHUTDOWN
REMOTE LEAVING CHILLED WATER TEMP AND CURRENT
LIMIT SETPOINTS (CONTACT CLOSURE)
VARIABLE ORIFICE CONTROL
PRE-ROTATION VANE CONTROL
STATUS / ALARM
CHILLER SOLENOID VALVES
OIL PUMP STARTER
OIL HEATER ON/OFF
CHILLED AND CONDENSER WATER PUMP STARTERS
COMPRESSOR
MOTOR START
MOTOR CONTROLLER
SHUTDOWN TO I/O BOARD
MULTIPLEXED DATA
ADDRESS
SOLID
STATE
STARTER
LOGIC
BOARD
COMPRESSOR
MOTOR
CURRENT
+ 24 VDC
+12 / -12 / +5 VDC
OIL PUMP VSD SPEED CONTROL
RS-232 / RS-485 SERIAL DATA
CHILLER TEMPERATURES AND PRESSURES
CONDENSER REFRIGERANT LEVEL
HIGH SPEED THRUST BEARING POSITION
REMOTE LEAVING CHILLED WATER TEMP AND
CURRENT LIMIT SETPOINTS (0-20mA, 4-20mA / 0 - 10VDC, 2-10VDC)
TRIGGER
BOARD
STATUS
TRIGGER
BOARD
CONTROL
LTC
I/O BOARD
HOT GAS VALVE
HEAT RECOVERY VALVE
HEAD PRESSURE VALVE
HEATING CONDENSER
FLOW SWITCH
HEATING CONDENSER
TEMPERATURES
MOTOR
MONITORING
BOARD
WINDING TEMPERATURES
BEARING TEMPERATURES
VIBRATION
MODBUS
SERIAL
DATA