TABLE 22 - LEAVING AND RETURN HEATING
CONDENSER WATER TEMPERATURE SENSOR
TEMP (°F) TEMP (°C) VIN
32.63 0.35 1.713
37.47 3.03 1.870
42.23 5.68 2.026
46.96 9.97 2.182
51.68 10.93 2.338
56.44 13.57 2.495
61.28 16.26 2.651
66.23 19.01 2.807
71.36 21.86 2.963
76.70 24.61 3.120
82.32 27.955 3.276
88.31 31.28 3.432
94.74 34.85 3.588
101.8 38.77 3.745
109.6 43.11 3.901
118.5 48.05 4.057
128.9 53.83 4.213
141.7 60.94 4.370
158.2 70.11 4.526