EasyManua.ls Logo

York OPTIVIEW YK - FIGURE 32 - Low Voltage Digital Inputs

York OPTIVIEW YK
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
96
FORM 160.54-M1
ISSUE DATE: 10/25/2019
SECTION 5 - MICROBOARD 031-03630-001
JCI COMPANY CONFIDENTIAL JOHNSON CONTROLS
FIGURE 32 - LOW VOLTAGE DIGITAL INPUTS
LD12827b
NOTE:
1. On new production chillers after June 2009, the Thermal type ow sensors are connected to Microboard J14 as shown above. Program
Jumpers JP10 through JP12 must be positioned on pins 2-3 and software version C.OPT.01.21.307 (and later) is required. On new
production chillers before June 2009, the Thermal type ow sensors are connected to Microboard J7 (See Figure 30 on page 94).
24VAC
Factory Mounted Evaporator
Thermal-Type Flow Sensor
(note 1)
3
2
4
2
4
2
4
1
24VAC
Factory Mounted Condenser
Thermal-Type Flow Sensor
(note 1)
3 1
24VAC
Factory Mounted
Heating Condenser
Thermal-Type Flow Sensor
(note 1)
3 1
NOT USED

Table of Contents

Related product manuals