152 Actual signals and parameters
0134
COMM RO WORD
0...65535 1 0
Free data location that can be written from serial link.
Used for relay output control.
See parameter 1401.
0135
COMM VALUE 1
-32768 … +32767 1 0
Free data location that can be written from serial link.
0136
COMM VALUE 2
-32768 … +32767 1 0
Free data location that can be written from serial link.
0137
PROCESS VAR 1
-1
Process variable 1
Defined by parameters in Group 34: Panel display.
0138
PROCESS VAR 2
-1
Process variable 2
Defined by parameters in Group 34: Panel display.
0139
PROCESS VAR 3
-1
Process variable 3
Defined by parameters in Group 34: Panel display.
0140
RUN TIME
0 … 499.99 kh 0.01 kh 0 kh
The drive’s accumulated running time in thousands of hours (kh). Cannot be
reset.
0141
MWH COUNTER
0 … 65535 MWh 1 MWh -
The drive’s accumulated power consumption in megawatt hours. Cannot be reset
0142
REVOLUTION CNTR
0 … 65535 Mrev 1 0
The motor’s accumulated revolutions in millions of revolutions. Can be reset by
pressing the UP and DOWN keys simultaneously when in the Parameters mode.
0143
DRIVE ON TIME HI
0 … 65535 days 1 day 0
The drive’s accumulated power-on-time in days. Cannot be reset.
0144
DRIVE ON TIME LO
00.00.00 … 23:59:58 2 s 0
The drives accumulated power-on-time in 2 second ticks (30 ticks = 60
seconds).
Shown in format hh.mm.ss.
Cannot be reset.
0145
MOTOR TEMP
-10...200 °C/
0...5000 Ohm /
0...1
10
Motor temperature in Celsius / PTC resistance in Ohms.
Applies only if motor temperature sensor is set up. See parameter 3501
SENSOR TYPE.
0158
PID COMM VALUE 1
Data received from fieldbus for PID control (PID1 and PID2).
Group 01: Operating data
Code Description Range Resolution Default S