180 Actual signals and parameters
1602
PARAMETER LOCK
0…2 1 1
Determines if the control panel can change parameter values.
This lock does not limit parameter changes made by macros.
This lock does not limit parameter changes written by fieldbus inputs.
This parameter value can be changed only if the correct pass code is entered. See
parameter 1603 PASS CODE.
0 = LOCKED – You cannot use the control panel to change parameter values.
The lock can be opened by entering the valid pass code to parameter 1603 PASS
CODE.
1 = OPEN – You can use the control panel to change parameter values.
2 = NOT SAVED – You can use the control panel to change parameter values, but
they are not stored in permanent memory.
Set parameter 1607 PARAM. SAVE to 1 (SAVE) to store changed parameter
values to memory.
1603
PASS CODE
0…65535 1 0
Entering the correct pass code allows you to change the parameter lock.
See parameter 1602 PARAMETER LOCK above.
Code 358 allows you to change the value of the parameter 1602 PARAMETER
LOCK once.
This entry reverts back to 0 automatically.
1604
FAULT RESET SEL
-5…7 1 0
Selects the source for the fault reset signal. The signal resets the drive after a fault trip
if the cause of the fault no longer exists.
0 = KEYPAD – Defines the control panel as the only fault reset source.
Fault reset is always possible with control panel.
1 = DI1 – Defines digital input DI1 as a fault reset source.
Activating the digital input resets the drive.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as a fault reset source.
See DI1 above.
7 = START/STOP – Defines the Stop command as a fault reset source.
Do not use this option when fieldbus communication provides the start, stop and
direction commands.
8 = COMM – Defines the fieldbus as a fault reset source.
The Command word is supplied through fieldbus communication.
The bit 4 of the Command word 1 (parameter 0301 FB CMD WORD 1) resets the
drive.
-1 = DI1(INV) – Defines an inverted digital input 1 as a fault reset source.
De-activating the digital input resets the drive.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as a fault
reset source.
See DI1(INV) above.
Group 16: System controls