EasyManua.ls Logo

ABB ACS320 - Page 339

ABB ACS320
442 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fieldbus control 339
* = Active low
For the 0xxxx registers:
Status is always readable.
Forcing is allowed by user configuration of the drive for fieldbus control.
Additional relay outputs are added sequentially.
The drive supports the following Modbus function codes for coils:
1xxxx Mapping – Modbus Discrete Inputs. The drive maps the following
information to the 1xxxx Modbus set called Modbus Discrete Inputs:
Bit-wise map of the
STATUS WORD (selected using parameter 5305 EFB CTRL
PROFILE). The first 32 inputs are reserved for this purpose.
Discrete hardware inputs, numbered sequentially beginning with input 33.
The following table summarizes the 1xxxx reference set:
00033 relay output 1 Relay Output 1 Relay Output 1 Relay Output 1
00034 relay output 2 Relay Output 2 Relay Output 2 Relay Output 2
00035 relay output 3 Relay Output 3 Relay Output 3 Relay Output 3
00036 relay output 4 Relay Output 4 Relay Output 4 Relay Output 4
Function Code Description
01 Read coil status
05 Force single coil
15 (0x0F Hex) Force multiple coils
Modbus
Ref.
Internal Location
(All Profiles)
(5305 = 0 or 2)
(5305 = 1)
10001 – Bit 0 RDY_ON READY
10002 Bit 1 RDY_RUN ENABLED
10003 – Bit 2 RDY_REF STARTED
10004 – Bit 3 TRIPPED RUNNING
10005 Bit 4 OFF_2_STA* ZERO_SPEED
10006 – Bit 5 OFF_3_STA* ACCELERATE
10007 – Bit 6 SWC_ON_INHIB DECELERATE
10008 – Bit 7 ALARM AT_SETPOINT
10009 – Bit 8 AT_SETPOINT LIMIT
10010 Bit 9 REMOTE SUPERVISION
10011 – Bit 10 ABOVE_LIMIT REV_REF
10012 Bit 11 EXT2 REV_ACT
10013 – Bit 12 RUN_ENABLE PANEL_LOCAL
10014 – Bit 13 N/A FIELDBUS_LOCAL
10015 – Bit 14 N/A EXT2_ACT
Modbus
Ref.
Internal Location
(All Profiles)
(5305 = 0)
(5305 = 1)
(5305 = 2)

Table of Contents

Other manuals for ABB ACS320

Related product manuals