366 Fault tracing
5030 Invalid request Contact your local ABB representative.
5031 Drive is not ready for
operation, eg due to low
DC voltage.
Check input power supply.
5032 Parameter error Contact your local ABB representative.
5040 Parameter download error.
Selected parameter set is
not in current parameter
backup file.
Perform upload function before download.
5041 Parameter backup file
does not fit into memory.
Contact your local ABB representative.
5042 Parameter download error.
Selected parameter set is
not in current parameter
backup file.
Perform upload function before download.
5043 No start inhibit
5044 Parameter backup file
restoring error
Check that file is compatible with drive.
5050 Parameter upload aborted Retry parameter upload.
5051 File error Contact your local ABB representative.
5052 Parameter upload has
failed.
Retry parameter upload.
5060 Parameter download
aborted
Retry parameter download.
5062 Parameter download has
failed.
Retry parameter download.
5070 Panel backup memory
write error
Contact your local ABB representative.
5071 Panel backup memory
read error
Contact your local ABB representative.
5080 Operation is not allowed
because drive is not in
local control mode.
Switch to local control mode.
5081 Operation is not allowed
because of active fault.
Check cause of fault and reset fault.
5083 Operation is not allowed
because parameter lock is
on.
Check parameter 1602 PARAMETER LOCK
setting.
5084 Operation is not allowed
because drive is
performing task.
Wait until task is completed and retry.
5085 Parameter download from
source to destination drive
has failed.
Check that source and destination drive types
are same, ie, ACS320. See the type
designation label of the drive.
5086 Parameter download from
source to destination drive
has failed.
Check that source and destination drive type
designations are the same. See type
designation labels of the drives.
ALARM CODE CAUSE WHAT TO DO